Sign In | Join Free | My udpf.com |
|
Place of Origin : QINGDAO , CHINA
Brand Name : KANGWEI
Certification : CCS,BV, IEC
Model Number : According to the design and technical demand
MOQ : 1SET
Packaging Details : CONTAINER ,WOODEN CASE
Delivery Time : Negotiate
Payment Terms : T/T, L/C
Supply Ability : 20SETS
Fuel : diesel oil ,heavy fuel oil,gas
Price : negotiated
speed : 550-750rpm
designing capacity : 1-20MW
power plant experience : 6 months engineering for 10MW power plant except in Africa
output voltage : depend on the enduser
fuel consumption : 201g/kwh
contral system : SCADA DCS
10 X 2000kW Heavy Fuel Oil Power Plant 500 Rpm 600 Rpm With Generating Sets
Applications:
cement, textile, mining or oil and gas industries etc.
Competitive Advantage:
Our experts in application engineering and project management are the key to achieving very short construction times , builds turn-key power plant with an output up to 60MW as base load power plant, peaking power plant or industrial self-captive power plant in cement, textile, mining or oil and gas industries etc.
The power fuel can be diesel oil, bio-diesel, heavy fuel oil (HFO)
G300 Statinary Generating Sets Main Specification | ||||||||
Model | 1000GF1 | 1250GF3 | 1350GF4 | 1400GF4 | ||||
Rated power, KW | 1000 | 1250 | 1350 | 1400 | ||||
Overload , KW | 1100 | 1375 | 1485 | 1540 | ||||
Rated voltage, V | 400/415/440/3300/6300/10500/13800 | |||||||
Rated current , A | ||||||||
Frequency , Hz | 50 | 60 | 50 | 60 | 50 | 60 | 50 | 60 |
Power factor | 0.8 Lagging | |||||||
Phase | 3 | |||||||
Diesel engine | G6300ZD6 | G6300ZD8 | G8300ZD6 | G6300ZD10 | G8300ZD10 | G8300ZD8 | G8300ZD10 | G8300ZD8 |
Rated power, KW | 1103 | 1470 | 1471 | 1471 | 1765 | 2000 | 1765 | 2000 |
Rated rev, rpm | 500 | 600 | 500 | 600 | 500 | 600 | 500 | 600 |
Alternator | 3 phase alternator | |||||||
voltage fluctuation rate% | <0.5 | <0.5 | ||||||
Frequency fluctuation rate, % | <0.5 | <0.5 | ||||||
Stable voltage regulating rate, % | ±1.0 | ±1.0 | ||||||
Transient voltage regulating rate, % | +20, -15 | +20, -15 | ||||||
Stable Frequency fluctuation rate, % | <3 | <0.5 | ||||||
Transient frequency regulating rate, % | +12, -10 | |||||||
Stablizing time, voltage , S | <4 | |||||||
Stablizing time, frequency , S | <3 | |||||||
voltage regulating method | automatic and munual | |||||||
Frequency regulating method | manual | |||||||
starting method | compressed air | |||||||
Lubricating method | pressue lubricating | |||||||
Cooking method | water cooling | |||||||
coupling | flexible | |||||||
Overdimension, mm | 3880*2150*3180 | 8470*2360*3060 | ||||||
Weight, Kg | 30000 | 35000 | 38000 |
G300 Statinary Generating Sets Main Specification | |||||||
1500GF6 | 1600GF5 | 1800GF7 | 2000GF8 | ||||
1500 | 1600 | 1800 | 2000 | ||||
1650 | 1760 | 1980 | 2200 | ||||
400/415/440/3300/6300/10500/13800 | |||||||
50 | 60 | 50 | 60 | 50 | 60 | 50 | 60 |
0.8 Lagging | |||||||
3 | |||||||
G8300ZD10 | G8300ZD8 | G8300ZD10 | G8300ZD8 | G8300ZD8 | G8300ZD8 | G8300ZD12 | G8300ZD8 |
1765 | 2000 | 1765 | 2000 | 2000 | 2000 | 2206 | 2000 |
500 | 600 | 500 | 600 | 600 | 600 | 600 | 600 |
3 phase alternator | |||||||
<0.5 | |||||||
<0.5 | |||||||
±1.0 | |||||||
20, -15 | |||||||
<0.5 | |||||||
+20, -15 | |||||||
<5 | |||||||
<4 | |||||||
automatic and munual | |||||||
manual | |||||||
compressed air | |||||||
pressue lubricating | |||||||
water cooling | |||||||
flexible | |||||||
8470*2360*3060 | |||||||
38000 | 42560 |
Remark
1. the generator voltage and frequency can be selected
2. rating for the generator set is based on the following standard conditions
air temperature :25℃
total barometric pressure 100kpa
charge air coolant temperature 25℃
relative humidity 30%
If test ambient conditions are not same as the standard ambient conditions, the power and fuel consumptions should be revised according to GB/T6072.1-2000
3. The generator set can operate under overload, intermittently for 1 hour every 12h, the fuel injection quantity is usualy locked in the rated power position
GN8320 Stationary Generating Sets Main Specification |
||||||||||
Model |
2400GF |
2500GF |
||||||||
Rated power, KW |
2400 |
2500 |
||||||||
Overload , KW |
2640 |
2750 |
||||||||
Rated voltage, V |
400 |
415 |
3300 |
6300 |
10500 |
400 |
415 |
3300 |
6300 |
10500 |
Rated current , A |
4330 |
4174 |
525 |
275 |
165 |
4511 |
4348 |
547 |
172 |
286 |
Frequency , Hz |
50 |
50 |
||||||||
Power factor |
0.8 Lagging |
0.8 Lagging |
||||||||
Phase |
3 |
3 |
||||||||
Diesel engine |
GN832000ZD |
GN8320ZD |
||||||||
Rated power, KW |
2648 |
2795 |
||||||||
Rated rev, rpm |
750 |
750 |
||||||||
Alternator |
3 phase alternator |
|||||||||
voltage fluctuation rate% |
±1.0 |
|||||||||
Frequency fluctuation rate, % |
+12, -10 |
|||||||||
Stable voltage regulating rate, % |
3 |
|||||||||
Transient voltage regulating rate, % |
+12, -10 |
|||||||||
Stable Frequency fluctuation rate, % |
4
|
|||||||||
Transient frequency regulating rate, % |
5 |
|||||||||
Stabilizing time, voltage , S |
+1 |
|||||||||
Stabilizing time, frequency , S |
+12, -10 |
|||||||||
voltage regulating method |
automatic and manual |
|||||||||
Frequency regulating method |
manual |
|||||||||
starting method |
compressed air |
|||||||||
Lubricating method |
pressure lubricating |
|||||||||
Cooking method |
water cooling |
|||||||||
coupling |
flexible |
|||||||||
Overdimension, mm |
8950*2570*6050 |
|||||||||
Weight, Kg |
45000 |
Remark
1. the generator voltage and frequency can be selected
2. rating for the generator set is based on the following standard conditions
air temperature :25℃
total barometric pressure
charge air coolant temperature
relative humidity
If test ambient conditions are not same as the standard ambient conditions, the power and fuel consumptions should be revised according to GB/T6072.1-2000
3. The generator set can operate under overload, intermittently for 1 hour every 12h, the fuel injection quantity is usualy locked in the rated power position
![]() |
10 X 2000kW LNG gas and Heavy Fuel Oil Power Plant with Generator 500 Rpm 600 Rpm 750 Rpm Images |